Арт.: 100-E80KY00

Iec 80 А контактор

IEC 80 A Contactor

Цена по запросу  — уточняйте актуальную стоимость
Lifecycle Status Active
Repair Options Available No
Altitude, max 3000 m of installation site
Ambient temperature Storage: -40...+70 (-40...+158)
Climatic withstand Category B according to IEC 60947-1, annex Q
Coil voltage 48 to 130V AC/DC

Технические характеристики

Lifecycle Status Active
Repair Options Available No
Altitude, max 3000 m of installation site
Ambient temperature Storage: -40...+70 (-40...+158)
Climatic withstand Category B according to IEC 60947-1, annex Q
Coil voltage 48 to 130V AC/DC
DIN fuses (gG) current rating Type 2 (per IEC 60947-4-1): 80A @ 690V, 60 kA available fault current
Electromagnetic compatibility IEC 60947-1 - Environment A and B (100-E09...E38 only.)
Features Panel mounting or mounting on 35 mm DIN rail, AC/DC electronic coil, Made of environmentally friendl
FLA 105A @ 600V, 3-phase per UL/CSA HVAC applications
Function Non-reversing contactor
General purpose current (enclosed) 80A @ 600V per UL/CSA
LRA 630 A @ 440-480V AC, 3-phase per UL/CSA HVAC applications
MCCB current rating Type 2 (per IEC 60947-4-1): 880A @ 400V, 70 kA available fault current
Number of auxiliary contacts as normally closed contact 0
Number of auxiliary contacts as normally open contact 0
Operating limits, dropout (≤0.60) x Us @ DC control
Operating limits, pick-up (0.85...1.1) x Us @ 50/60 Hz
Operating time, closing delay 42 ms
Operating time, opening delay 17 ms
Optional accessories Side-or front-mount auxiliary contacts, Mechanical interlocks, IP20 terminal shields, Connecting bar
Optional overload relays Electronic
Protection class Contactor main contact: IP2X (100-E40...E96 meet IP2X when used with 100-ESC...terminal shrouds.)
Rated control supply voltage at AC 50 Hz 48 V
Rated control supply voltage at AC 60 Hz 48 V
Rated control supply voltage at DC 48 V
Rated impulse voltage withstand (Uimp) 8 kV
Rated isolation voltage (Ui) 600V per UL, CSA
Rated operational current and power 56A @ 115V AC, 500000 electrical ops, 1-phase per UL/CSA elevator duty
Rated operational current and power (enclosed) 89A @ 250V DC, with 3-poles in series per UL/CSA
Rated operational current (Ie) 85A @ 690V, AC-1 active power load (50/60 Hz), ambient temperature 70 °C (158 °F)
Rated operational power (Pe) 90 kW @ 415V, AC-1 active power load (50/60 Hz), ambient temperature 40 °C (104 °F)
Rated voltage (Ue) 24V @ 48V, 110V @ 220V, 440V DC
Rating for switching AC motors 3-poles: 75Hp @ 575V, AC-2, AC-3 (60 Hz)
Shock resistance IEC 60068-2-27
Standard coil, hold-in 4VA/2 W @ 48...130V AC/DC
Standard coil, pick-up 40VA/40 W @ 48…130V AC/DC
Switching of DC loads 3-poles in series: 125A @ 220V (Shunt-wound motors starting, reverse current breaking, reversing, st
Switching of lighting loads Tungsten lA: 105A @ 600V, 3-phase (break all lines) per UL/CSA
Switching of power transformers Apparent power: 99 kVA @ 600V @ 60Hz (n = 20)
Type of electrical connection of main circuit Screw connection
UL class J and CSA HRCI-J fuses rating Type 1 Combination (per UL 60947 and CSA 22.2 No. 14): 200A @ 600V, 100 kA available fault current
UL class RK5 fuses rating Type 1 Combination (per UL 60947 and CSA 22.2 No. 14): 200A @ 600V, 10 kA available fault current
UL inverse-time circuit breaker Type 1 Combination (per UL 60947 and CSA 22.2 No. 14): 250A @ 600V, 50 kA available fault current
Vibration resistance IEC 60068-2-6
Voltage type for actuating AC/DC

Запросить цену на Iec 80 А контактор

Заполните форму — ответим с актуальной ценой и сроком поставки в течение рабочего дня